F.352 CO limit inside appliance exceeded

Critical severity Vitodens 200-W B2HE

What the control is telling you

Burner in a fault state.

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Likely causes

  • Flue recirculation
  • Leaks
  • Water pocket
  • Restriction or blockage

Test and repair steps

  1. Check the whole flue path for recirculation, leaks, water pockets from insufficient fall, constrictions and blockages.
  2. Repair the flue system.
  3. Reset the appliance.

Models that show this code

3 models in Vitodens 200-W B2HE

B2HE-120B2HE-150B2HE-85

Other codes on the same units

  • F.348 Gas modulation valve fault
  • F.349 Air mass flow not detected correctly
  • F.350 Ionization current outside permitted range (BCU)
  • F.351 Ionization current outside permitted range (BCU)
  • F.353 Insufficient gas supply, output reduced
  • F.354 Gas modulation valve tolerance outside range
  • F.355 Analogue signal reference check: flame signal at start
  • F.357 Insufficient gas supply

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.