Viessmann · Boiler
F.369 Flame loss right after ignition (safety time)
What the control is telling you
Burner in a fault state.
Applies to: Vitodens 200-W B2HE 85, 120, 150, 199
Likely causes
- Low gas pressure
- Flue recirculation
- Electrode gap/dirt
Test and repair steps
- Check gas supply pressure.
- Check the balanced flue for recirculation.
- Check electrode clearance to flame body and contamination.
- Reset the appliance.
Models that show this code
4 models in Vitodens 200-W B2HE
Other codes on the same units
- F.359 No ignition spark
- F.361 No or weak flame signal at burner start
- F.366 Gas valve supply does not switch off
- F.367 Gas valve supply does not switch off
- F.370 Fuel or modulation valve will not close
- F.372 Repeated flame loss during calibration
- F.373 Heat transfer too low during calibration
- F.377 Ionization post-adjustment conditions not met
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.