Viessmann · Boiler

EC 67 or 195 Parameter fault at calibration

High severity Vitodens 200-W B2HA

What the control is telling you

Burner in fault mode. Parameter fault during calibration. Detailed code 67 or 195.

Applies to: Vitodens 200-W B2HA 45, 60

Likely causes

  • Parameter fault during calibration

Test and repair steps

  1. Press reset button R.
  2. If the fault persists, replace the boiler coding card and press reset button R.

Other codes on the same units

  • F3 139 Flame signal present at burner start
  • F8 148 Gas valve closes too late
  • F9 151 or 152 Fan speed too low at burner start
  • EA 193 Ionization current deviation during calibration
  • EB 194 Repeated flame loss at calibration
  • ED 191 Internal burner control fault
  • EE 132 Flame signal missing or weak at burner start
  • EF 138 Flame lost during safety time

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 75. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.