Viessmann · Boiler
EF 138 Flame lost during safety time
What the control is telling you
Burner in fault mode. Flame lost immediately after it has built, during the safety time. Detailed code 138.
Applies to: Vitodens 200-W B2HA 45, 60
Likely causes
- Gas supply pressure or gas regulator problem
- Flue gas recirculation
- Ionization electrode distance or contamination
Test and repair steps
- Check gas supply, gas pressure and gas regulator.
- Check flue gas/ventilation air system for flue gas recirculation.
- Check ionization electrode distance to burner gauze assembly (see page 22) and contamination; replace if required.
- Press reset button R.
Other codes on the same units
- F3 139 Flame signal present at burner start
- F8 148 Gas valve closes too late
- F9 151 or 152 Fan speed too low at burner start
- EA 193 Ionization current deviation during calibration
- EB 194 Repeated flame loss at calibration
- EC 67 or 195 Parameter fault at calibration
- ED 191 Internal burner control fault
- EE 132 Flame signal missing or weak at burner start
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 76. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.