Viessmann · Boiler
EA 193 Ionization current deviation during calibration
What the control is telling you
Burner in fault mode. Ionization current outside permissible range during calibration; deviation from previous level too great. Detailed code 193.
Applies to: Vitodens 200-W B2HA 45, 60
Likely causes
- Flue gas recirculation
- Dusty combustion air in open flue mode
Test and repair steps
- Check flue system and remedy flue gas recirculation if required.
- In open flue mode, prevent very dusty combustion air conditions.
- Press reset button R.
- After several unsuccessful resets, replace the boiler coding card and press reset button R.
Other codes on the same units
- F3 139 Flame signal present at burner start
- F8 148 Gas valve closes too late
- F9 151 or 152 Fan speed too low at burner start
- EB 194 Repeated flame loss at calibration
- EC 67 or 195 Parameter fault at calibration
- ED 191 Internal burner control fault
- EE 132 Flame signal missing or weak at burner start
- EF 138 Flame lost during safety time
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 75. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.