Viessmann · Boiler

EA Ionization current outside range during calibration

High severity Vitocrossal 300 CU3A

What the control is telling you

Burner is in fault mode because the ionization current is outside the permissible range during calibration. The deviation from the previous level is too large.

Applies to: Vitocrossal 300 CU3A 26 to 199

Likely causes

  • Flue gas recirculation
  • Dusty combustion air in open flue mode
  • Faulty boiler coding card after repeated resets

Test and repair steps

  1. Check the flue system and remedy flue gas recirculation if required.
  2. In open flue mode, prevent very dusty conditions for the combustion air.
  3. Press reset button R.
  4. After several unsuccessful resets, replace the boiler coding card and press reset button R.

Models that show this code

11 models in Vitocrossal 300 CU3A

CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94

Other codes on the same units

  • E7 Ionization current too low during calibration
  • E8 Ionization current outside permissible range
  • EB Repeated flame loss during calibration

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 90. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.