Viessmann · Boiler

E8 Ionization current outside permissible range

High severity Vitocrossal 300 CU3A

What the control is telling you

Burner is in fault mode because the ionization current is outside the permissible range.

Applies to: Vitocrossal 300 CU3A 26 to 199

Likely causes

  • Gas supply problem (pressure or gas flow limiter)
  • Gas train or connecting lead fault
  • Wrong gas type allocation
  • Ionization electrode distance or contamination

Test and repair steps

  1. Check the gas supply gas pressure and gas flow limiter.
  2. Check the gas train and connecting lead.
  3. Check the gas type allocation (see page 17).
  4. Check the ionization electrode distance to the burner gauze assembly (see page 23).
  5. Check the electrode for contamination.
  6. Press reset button R.

Models that show this code

11 models in Vitocrossal 300 CU3A

CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94

Other codes on the same units

  • E7 Ionization current too low during calibration
  • EA Ionization current outside range during calibration
  • EB Repeated flame loss during calibration

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 90. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.