E8 Ionization current outside permissible range
What the control is telling you
Burner is in fault mode because the ionization current is outside the permissible range.
Applies to: Vitocrossal 300 CU3A 26 to 199
Likely causes
- Gas supply problem (pressure or gas flow limiter)
- Gas train or connecting lead fault
- Wrong gas type allocation
- Ionization electrode distance or contamination
Test and repair steps
- Check the gas supply gas pressure and gas flow limiter.
- Check the gas train and connecting lead.
- Check the gas type allocation (see page 17).
- Check the ionization electrode distance to the burner gauze assembly (see page 23).
- Check the electrode for contamination.
- Press reset button R.
Models that show this code
11 models in Vitocrossal 300 CU3A
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 90. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.