Viessmann · Boiler

E7 192 Ionization current too low at calibration

High severity Vitodens 200-W B2HA

What the control is telling you

Burner in fault mode. Ionization current too low during calibration. Detailed code 192.

Applies to: Vitodens 200-W B2HA 45, 60

Likely causes

  • Ionization current too low during calibration
  • Electrode contaminated or too far from burner gauze
  • Connecting lead or plug-in connections faulty
  • Flue gas recirculation

Test and repair steps

  1. Check ionization electrode distance to burner gauze assembly (see page 22).
  2. Check electrode for contamination.
  3. Check connecting lead and plug-in connections.
  4. Check flue system and remedy flue gas recirculation if required.
  5. Press reset button R.

Other codes on the same units

  • E1 202 Ionization current too high at calibration
  • E2 201 Heating water flow rate too low during calibration
  • E3 204 Heat transfer too low at calibration
  • E5 226 Flame amplifier fault
  • E8 189 Ionization current outside permissible range
  • F1 135 Maximum flue gas temperature exceeded
  • F2 129 Fixed high limit switch open
  • F3 139 Flame signal present at burner start

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 75. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.