E7 Ionization current too low during calibration
What the control is telling you
Burner is in fault mode because the ionization current is too low during calibration.
Applies to: Vitocrossal 300 CU3A 26 to 199
Likely causes
- Ionization electrode too far from burner gauze or contaminated
- Faulty connecting lead or plug-in connections
- Flue gas recirculation
Test and repair steps
- Check the ionization electrode distance to the burner gauze assembly (see page 23).
- Check the electrode for contamination.
- Check the connecting lead and plug-in connections.
- Check the flue system and remedy flue gas recirculation if required.
- Press reset button R.
Models that show this code
11 models in Vitocrossal 300 CU3A
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 90. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.