Viessmann · Boiler
F1 135 Maximum flue gas temperature exceeded
What the control is telling you
Burner in fault mode. Maximum flue gas temperature exceeded, 230°F (110°C) limit. Detailed code 135.
Applies to: Vitodens 200-W B2HA 45, 60
Likely causes
- Low heating system fill level
- Air in system
- Circulation pump fault
- Boiler water temperature sensor or cable faulty
Test and repair steps
- Check heating system fill level.
- Bleed air from system.
- Check circulation pump.
- Check boiler water temperature sensor and cable.
- Press reset button R after vent system has cooled down.
Other codes on the same units
- E3 204 Heat transfer too low at calibration
- E5 226 Flame amplifier fault
- E7 192 Ionization current too low at calibration
- E8 189 Ionization current outside permissible range
- F2 129 Fixed high limit switch open
- F3 139 Flame signal present at burner start
- F8 148 Gas valve closes too late
- F9 151 or 152 Fan speed too low at burner start
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 76. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.