Viessmann · Boiler

E8 189 Ionization current outside permissible range

High severity Vitodens 200-W B2HA

What the control is telling you

Burner in fault mode. Ionization current outside permissible range. Detailed code 189.

Applies to: Vitodens 200-W B2HA 45, 60

Likely causes

  • Gas supply pressure or gas flow limiter problem
  • Gas valve or connecting lead faulty
  • Wrong gas type allocation
  • Ionization electrode too far or contaminated

Test and repair steps

  1. Check gas supply, gas pressure and gas flow limiter, gas valve and connecting lead.
  2. Check allocation of gas type (see page 15).
  3. Check ionization electrode distance to burner gauze assembly (see page 22) and for contamination.
  4. Press reset button R.

Other codes on the same units

  • E1 202 Ionization current too high at calibration
  • E2 201 Heating water flow rate too low during calibration
  • E3 204 Heat transfer too low at calibration
  • E5 226 Flame amplifier fault
  • E7 192 Ionization current too low at calibration
  • F1 135 Maximum flue gas temperature exceeded
  • F2 129 Fixed high limit switch open
  • F3 139 Flame signal present at burner start

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 75. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.