Viessmann · Boiler
EE 132 Flame signal missing or weak at burner start
What the control is telling you
Burner in fault mode. At burner start, flame signal is missing or too weak. Detailed code 132.
Applies to: Vitodens 200-W B2HA 45, 60
Likely causes
- Gas supply pressure or gas regulator problem
- Gas train fault
- Ionization electrode or cable faulty
- Ignition leads, electrode or gap faulty
- Condensate drain blocked
Test and repair steps
- Check gas supply, gas pressure and gas regulator.
- Check gas train.
- Check ionization electrode and connecting cable.
- Check ignition leads to ignition module and ignition electrode.
- Check ignition electrode gap and contamination (see page 22).
- Check condensate drain.
- Press reset button R.
Other codes on the same units
- F3 139 Flame signal present at burner start
- F8 148 Gas valve closes too late
- F9 151 or 152 Fan speed too low at burner start
- EA 193 Ionization current deviation during calibration
- EB 194 Repeated flame loss at calibration
- EC 67 or 195 Parameter fault at calibration
- ED 191 Internal burner control fault
- EF 138 Flame lost during safety time
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 76. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.