Viessmann · Boiler

EC Safety relay fault

Critical severity Versatronik 300 Cascade Control

What the control is telling you

Fault on the safety relay.

Applies to: Versatronik 300 cascade control

Models that show this code

2 models in Versatronik 300 Cascade Control

704083704092

Other codes on the same units

  • d3 EA1 module communication failure
  • E1 Gas valve 1 / gas pressure monitoring 1 fault
  • E2 Gas valve 2 / gas pressure monitoring 2 fault
  • E3 Safety chain error
  • A AUX demand active indicator
  • ED Ignition relay fault
  • EE Internal feedback error, gas safety valves
  • EF Internal feedback error, gas safety valves

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Versatronik 300 Cascade Control manual, p. 41. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.