Rinnai · Boiler

Block 01 External safety contact open

Medium severity E-Combi (E50CRNE75CRN/E75CRPE110CRN/E110CRP)

What the control is telling you

Temporary block: the external safety contact wired to the boiler is open, so the burner is held off.

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Likely causes

  • External safety device tripped
  • Link between terminals 24 and 25 missing or broken

Test and repair steps

  1. Find out why the external safety device is open and correct that condition.
  2. If no device is fitted, check or restore the wire link across terminals 24 and 25.
  3. Confirm the block clears and the boiler runs.

Other codes on the same units

  • E37 Return sensor T2 open
  • E69 No or incorrect display
  • A XX De-aeration running
  • Block 05 Outdoor sensor not connected
  • Block 60 Wrong minimum/maximum power parameter
  • Block 67 Supply/return sensor difference with burner off
  • Block 85 No water flow detected
  • COdE Access code entry

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-72 (15.1, 15.2). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.