Rinnai · Boiler

Block 67 Supply/return sensor difference with burner off

Medium severity E-Combi (E50CRNE75CRN/E75CRPE110CRN/E110CRP)

What the control is telling you

Temporary block: a temperature difference between supply and return sensors was seen while the burner is not running. It clears when the difference disappears.

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Likely causes

  • Defective supply (T1) or return (T2) sensor
  • External heat source warming one sensor

Test and repair steps

  1. Check the resistance of the supply and return sensors and replace the faulty one.
  2. Look for an outside heat source acting on the pipes or sensors and remove it.

Other codes on the same units

  • A XX De-aeration running
  • Block 01 External safety contact open
  • Block 05 Outdoor sensor not connected
  • Block 60 Wrong minimum/maximum power parameter
  • Block 85 No water flow detected
  • COdE Access code entry
  • Copy Factory settings restored
  • ERRO Error chapter

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-72 (15.1, 15.2). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.