NTI · Boiler

5 P2 2nd ignition failed

High severity TRX

What the control is telling you

Second ignition attempt was unsuccessful. Warning.

Applies to: TRX150

Likely causes

  • Gas pressure out of range
  • Faulty gas valve wiring
  • Faulty flame sensor
  • Faulty igniter transformer or igniter
  • Unstable flame

Test and repair steps

  1. Monitor gas pressure during operation. Natural gas should be 3.5 to 10.5 in. WC. For LP, 8 to 13 in. WC.
  2. Check the gas valve wire and make sure the connection is secure.
  3. Check the flame detection sensor and its connections. Signal should be more than 2.5 DC before ignition and less than 2.5 DC after ignition.
  4. Check the igniter transformer connection.
  5. Clean the spark igniter with steel wool. Check the gap (2/16 to 3/16 in.).
  6. Replace the spark igniter if damaged.
  7. Make sure the flame is stable when lit.
  8. If the problem continues, replace the main control.

Models that show this code

5 models in TRX

TRX085TRX110CTRX150TRX199TRX199C

Other codes on the same units

  • 05 01 Ignition lockout after 3 failed attempts
  • 05 02 Flame detected with gas valve closed
  • 05 04 10 flame lifts in one operating cycle
  • 5 P1 1st ignition failed
  • 5 P3 Flame loss during run
  • 5 P6 3rd and 4th ignition failed
  • 06 02 Exhaust temperature above 204 °F (96 °C)
  • 06 03 APS open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: NTI TRX150 manual, p. 86. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.