06 02 Exhaust temperature above 204 °F (96 °C)
What the control is telling you
Exhaust NTC reads vent temperature above 204 °F. Manual reset.
Applies to: TRX150
Likely causes
- Faulty exhaust sensor
- Blocked exhaust vent
- Scaled or dirty heat exchanger
- Faulty control or heat exchanger
Test and repair steps
- Press Reset to clear the code.
- Check the exhaust temperature sensor and make sure the connections are secure.
- Check the sensor resistance. If it is zero, replace the sensor.
- Compare the flue gas temperature with the reading on parameter 834. If parameter 834 is much higher, replace the flue sensor.
- Check the exhaust vent for blockage.
- If the problem continues, check the combustion chamber and clean if needed. Descale the heat exchanger.
- If the problem continues, replace the control.
- If the problem still continues, replace the heat exchanger.
Models that show this code
5 models in TRX
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 87. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.