NTI · Boiler

06 03 APS open

High severity TRX

What the control is telling you

Air pressure switch (APS) is open. Reset to clear.

Applies to: TRX150

Likely causes

  • Loose APS or controller connection
  • Faulty APS
  • Damaged or disconnected APS hose
  • Blocked condensate line or exhaust vent

Test and repair steps

  1. Press Reset to clear the code.
  2. Check the APS and main controller connections. Make sure all are secure.
  3. Check the APS resistance. If it is not zero, replace the switch.
  4. Check the APS hose. Make sure it is connected and in good condition.
  5. Check the condensate line and termination for blockages.
  6. Check the exhaust vent for blockages.
  7. If the problem continues, replace the main control.

Models that show this code

5 models in TRX

TRX085TRX110CTRX150TRX199TRX199C

Other codes on the same units

  • 05 04 10 flame lifts in one operating cycle
  • 5 P1 1st ignition failed
  • 5 P2 2nd ignition failed
  • 5 P3 Flame loss during run
  • 5 P6 3rd and 4th ignition failed
  • 06 02 Exhaust temperature above 204 °F (96 °C)
  • 06 05 Exhaust NTC circuit open or short circuit
  • 6 12 Insufficient fan speed

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: NTI TRX150 manual, p. 87. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.