NTI · Boiler
05 04 10 flame lifts in one operating cycle
What the control is telling you
Flame lifted off the burner ten times in one cycle. Manual reset.
Applies to: TRX150
Likely causes
- Gas pressure out of range
- Faulty gas valve wiring
- Faulty flame sensor
- Blocked vent terminations
- Unstable flame
Test and repair steps
- Press Reset to clear the code.
- Monitor gas pressure during operation. It should be 3.5 to 10.5 in. WC.
- Check the gas valve wire and make sure the connection is secure.
- Check the flame detection sensor and its connections. Signal should be more than 2.5 DC before ignition and less than 2.5 DC after ignition.
- Check the vent terminations for blockages.
- Make sure the flame is stable when lit.
- If the problem continues, replace the main control.
Models that show this code
5 models in TRX
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 86. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.