NTI · Boiler
05 01 Ignition lockout after 3 failed attempts
What the control is telling you
The boiler locks out after the 3rd consecutive failed ignition attempt. It is also used to test the ignition circuit during first start-up.
Applies to: TRX150 and related TRX models
Likely causes
- Gas supply not open or gas pressure too low
- Gas leak at a connection
- Ignition device or flame sensing problem
- Post-purge too short before the igniter is reactivated
Test and repair steps
- Confirm the gas valve is open and gas pressure is present at the inlet.
- Check all gas connection seals, including the boiler connection, and eliminate any leak.
- Make sure the combustion fan post-purges for at least 5 seconds before the igniter reactivates.
- Set the room thermostat back to normal after the error appears.
- Press RESET to clear Error 501. The display should show OK.
- Restart the boiler by selecting CH or DHW.
Models that show this code
5 models in TRX
Other codes on the same units
- 4 12 Room sensor open or short circuit, Zone 2
- 4 13 Room sensor open or short circuit, Zone 3
- 4 30 Detected accessory wired to BUS connection
- 4 31 Code 431 (no description printed)
- 05 02 Flame detected with gas valve closed
- 05 04 10 flame lifts in one operating cycle
- 5 P1 1st ignition failed
- 5 P2 2nd ignition failed
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 83. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.