05 02 Flame detected with gas valve closed
What the control is telling you
Flame signal is present while the gas valve is closed. Auto reset.
Applies to: TRX150
Likely causes
- Faulty flame detection electrode
- Faulty main PCB
Test and repair steps
- If it returns, disconnect the flame detection electrode, then press Reset.
- If the error does not return, replace the flame detection electrode.
- If it returns again, replace the main PCB.
Models that show this code
5 models in TRX
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 86. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.