Navien · Heat pump

P7 Indoor coil freeze protection (T2)

High severity Navien NAZ

What the control is telling you

The indoor coil sensor T2 read below 0°C (32°F).

Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)

Likely causes

  • Low charge or leak
  • Cooling run at low outdoor temperature
  • Poor airflow / dirty coil
  • T2 sensor drift
  • Indoor PCB fault

Test and repair steps

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Look at the indoor coil. Iced up: check airflow (filter, blower) and the refrigerant side.
  3. No ice measure the T2 sensor and compare with the 7.3 R-T Table, p.72. Replace it if it has drifted.
  4. Check for a leak or low charge.
  5. Sensor and system good replace the indoor PCB.

Models that show this code

2 models in Navien NAZ

NAZ17V36NAZ17V60

Other codes on the same units

  • P3 Compressor drive overcurrent
  • P4 Discharge temperature too high
  • P5 Outdoor coil too hot in cooling
  • P6 Compressor drive (IPM) module protection
  • P8 Drive module (IPM) overheating
  • P9 Outdoor fan motor fault
  • ATL Outdoor temperature outside operating range
  • FA Outdoor board memory (EEPROM) fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.15, p.48. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.