Navien · Heat pump

FA Outdoor board memory (EEPROM) fault

High severity Navien NAZ

What the control is telling you

A chip on the outdoor PCB has failed. There is nothing to adjust in the field.

Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)

Likely causes

  • Defective outdoor PCB

Test and repair steps

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Replace the outdoor PCB.

Models that show this code

2 models in Navien NAZ

NAZ17V36NAZ17V60

Other codes on the same units

  • P7 Indoor coil freeze protection (T2)
  • P8 Drive module (IPM) overheating
  • P9 Outdoor fan motor fault
  • ATL Outdoor temperature outside operating range
  • FB Drive chip memory (EEPROM) fault
  • FC Drive module temperature sensor fault
  • FD Pressure sensor not detected
  • FE T3 or T5 probe out of position

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.4, p.32. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.