Navien · Heat pump

P8 Drive module (IPM) overheating

High severity Navien NAZ

What the control is telling you

The module temperature went over 90°C (194°F).

Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)

Likely causes

  • Cooling cover plate loose
  • Dried or uneven thermal paste
  • PCB fault

Test and repair steps

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Make sure the refrigerant cooling cover over the drive module is screwed down tight.
  3. Remove the cover and check the white thermal paste. Re-apply it if uneven.
  4. Run the unit and watch. Still tripping: replace the outdoor PCB.

Models that show this code

2 models in Navien NAZ

NAZ17V36NAZ17V60

Other codes on the same units

  • P4 Discharge temperature too high
  • P5 Outdoor coil too hot in cooling
  • P6 Compressor drive (IPM) module protection
  • P7 Indoor coil freeze protection (T2)
  • P9 Outdoor fan motor fault
  • ATL Outdoor temperature outside operating range
  • FA Outdoor board memory (EEPROM) fault
  • FB Drive chip memory (EEPROM) fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.16, p.49. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.