Navien · Heat pump

P5 Outdoor coil too hot in cooling

High severity Navien NAZ

What the control is telling you

The T3 coil sensor read over 60°C (140°F) in cooling.

Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)

Likely causes

  • Dirty or blocked outdoor coil
  • Outdoor fan not moving enough air
  • Low-side restriction
  • Bad T3 sensor or PCB reading

Test and repair steps

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Check the T3 sensor plug and resistance (7.3 R-T Table, p.72).
  3. Clean the outdoor coil and clear anything blocking airflow. Check for air short-cycling.
  4. Look for a low-side restriction (kinked line, plugged drier, closed valve).
  5. Compare the T3 reading on the CHK display with an infrared reading. Good sensor, wrong reading: replace the PCB.
  6. Still happening check the refrigerant side (poor evaporation, worn compressor).

Models that show this code

2 models in Navien NAZ

NAZ17V36NAZ17V60

Other codes on the same units

  • P1 High pressure switch opened
  • P2 Low pressure protection
  • P3 Compressor drive overcurrent
  • P4 Discharge temperature too high
  • P6 Compressor drive (IPM) module protection
  • P7 Indoor coil freeze protection (T2)
  • P8 Drive module (IPM) overheating
  • P9 Outdoor fan motor fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.13, p.43-44. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.