Navien · Heat pump
P5 Outdoor coil too hot in cooling
What the control is telling you
The T3 coil sensor read over 60°C (140°F) in cooling.
Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)
Likely causes
- Dirty or blocked outdoor coil
- Outdoor fan not moving enough air
- Low-side restriction
- Bad T3 sensor or PCB reading
Test and repair steps
- Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
- Check the T3 sensor plug and resistance (7.3 R-T Table, p.72).
- Clean the outdoor coil and clear anything blocking airflow. Check for air short-cycling.
- Look for a low-side restriction (kinked line, plugged drier, closed valve).
- Compare the T3 reading on the CHK display with an infrared reading. Good sensor, wrong reading: replace the PCB.
- Still happening check the refrigerant side (poor evaporation, worn compressor).
Models that show this code
2 models in Navien NAZ
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.13, p.43-44. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.