Navien · Heat pump
P3 Compressor drive overcurrent
What the control is telling you
The PCB measured too much running current. Trip points: 24K and 36K 26 A, 48K and 60K 32 A.
Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)
Likely causes
- Loose compressor or fan motor wiring
- Running far outside its range (hot-day cooling / cold-day heating)
- Dirty or blocked outdoor coil, units too close, air short-cycling
- Restriction on the high side (kinked line, stuck valve, service valve closed)
- Overcharge
- Air or nitrogen in the system
- PCB current reading wrong
Test and repair steps
- Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
- Tighten the compressor and fan motor wiring.
- Check the outdoor coil and clearances.
- Make sure both service valves are fully open and look for kinked or crushed lines.
- Check charge. Overcharged: recover some refrigerant.
- Signs of air or nitrogen (high head, high discharge temp, noisy): recover, evacuate and recharge by weight. Recover the R-454B charge with A2L-rated equipment before opening the sealed system.
- Clamp the line current and compare with parameter 20 on the CHK display. Close = compressor or system problem. Far apart = replace the PCB.
Models that show this code
2 models in Navien NAZ
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.11, p.38-39. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.