Navien · Heat pump
L0 DC bus voltage too low
What the control is telling you
The inverter DC bus voltage on the outdoor board is out of range.
Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)
Likely causes
- Supply voltage problem
- Outdoor PCB fault
Test and repair steps
- Measure line voltage at the unit. Fix the supply if it is off.
- Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
- Supply is good and the code returns replace the outdoor PCB.
Models that show this code
2 models in Navien NAZ
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.20, p.54. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.