Navien · Heat pump
H6 Lockout: high discharge temperature (P4 repeated)
What the control is telling you
P4 happened 3 times within 100 minutes and the unit has stopped.
Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)
Likely causes
- Same as P4: low charge, restriction, coil, air in system
Test and repair steps
- Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
- Check the T5 sensor plug and resistance (7.3 R-T Table, p.72).
- Check the outdoor coil for dirt, blocked discharge or air short-cycling.
- Look for a low-side restriction kinked suction line, plugged filter drier, closed valve, frost on the return line.
- Put gauges on. Return gas pressure is normally 0.7-0.9 MPa. Low = undercharge or leak: find the leak and recharge. Recover the R-454B charge with A2L-rated equipment before opening the sealed system.
- Check for air or nitrogen in the system.
- Compare parameter 08 (T5) with an infrared reading on the discharge line. Good sensor but wrong reading: replace the PCB.
Models that show this code
2 models in Navien NAZ
Other codes on the same units
- H2 Lockout: high pressure switch (P1 repeated)
- H3 Lockout: high pressure in heating (PD repeated)
- H4 Lockout: drive module overheating (P8 repeated)
- H5 Lockout: low pressure (P2 repeated)
- H7 Lockout: low discharge superheat (PC repeated)
- H8 Lockout: T3 probe off the pipe (FE repeated)
- L0 DC bus voltage too low
- L1 DC bus voltage too high
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.12, p.40-42. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.