Navien · Heat pump
H2 Lockout: high pressure switch (P1 repeated)
What the control is telling you
P1 happened 3 times within 150 minutes and the unit has stopped.
Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)
Likely causes
- Same as P1: coil airflow, restriction, overcharge, switch or wiring
Test and repair steps
- Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
- Check the high pressure switch wiring and plug.
- Check the outdoor coil dirt, blocked airflow, air short-cycling back into the unit.
- Put gauges on and run it. Look for restriction, poor vacuum or overcharge if head pressure is high.
- Pressures normal unplug the switch and ohm it. Open (infinite) = replace the switch. 0 Ω = replace the outdoor PCB.
Models that show this code
2 models in Navien NAZ
Other codes on the same units
- F8 T7 sensor: condensate risk on the cooling plate
- F9 Line voltage too low or too high
- H0 Communication fault between chips on the outdoor PCB
- H1 Lockout: outdoor coil too hot (P5 repeated)
- H3 Lockout: high pressure in heating (PD repeated)
- H4 Lockout: drive module overheating (P8 repeated)
- H5 Lockout: low pressure (P2 repeated)
- H6 Lockout: high discharge temperature (P4 repeated)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.9, p.35-36. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.