Navien · Heat pump

H7 Lockout: low discharge superheat (PC repeated)

High severity Navien NAZ

What the control is telling you

PC happened 3 times within 200 minutes and the unit has stopped.

Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)

Likely causes

  • Same as PC

Test and repair steps

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Measure the T5 and T3 sensors against the 7.3 R-T Table, p.72. Replace a bad one.
  3. Restart the unit. Every minute, compare an infrared reading on the discharge line and coil with parameters 08 (T5) and 06 (T3), until it stops.
  4. Readings do not match the CHK display replace the outdoor PCB.
  5. Readings match and T5 minus T3 is not 5°C (9°F) or less: replace the outdoor PCB.
  6. T5 minus T3 really is 5°C (9°F) or less: liquid is getting back to the compressor. Look for overcharge, restriction or air in the lines.

Models that show this code

2 models in Navien NAZ

NAZ17V36NAZ17V60

Other codes on the same units

  • H3 Lockout: high pressure in heating (PD repeated)
  • H4 Lockout: drive module overheating (P8 repeated)
  • H5 Lockout: low pressure (P2 repeated)
  • H6 Lockout: high discharge temperature (P4 repeated)
  • H8 Lockout: T3 probe off the pipe (FE repeated)
  • L0 DC bus voltage too low
  • L1 DC bus voltage too high
  • P1 High pressure switch opened

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.18, p.52-53. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.