Navien · Heat pump

P2 Low pressure protection

High severity Navien NAZ

What the control is telling you

The pressure sensor read below 0.2 MPa (about 29 psi).

Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)

Likely causes

  • Low charge or leak
  • Poor airflow over the evaporating coil
  • Restriction in the system
  • Bad pressure sensor or wiring
  • PCB fault

Test and repair steps

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Check the pressure sensor plug and wiring.
  3. Check airflow over the evaporating coil (filter, blower, dirty coil).
  4. Put gauges on, run the unit and compare the gauge reading with parameter 16 on the CHK display.
  5. Gauge and display far apart replace the pressure sensor.
  6. Both agree and are outside the limit system problem. Look for a leak, low charge, restriction or poor vacuum.
  7. Both agree and are inside the limit replace the outdoor PCB.

Models that show this code

2 models in Navien NAZ

NAZ17V36NAZ17V60

Other codes on the same units

  • H8 Lockout: T3 probe off the pipe (FE repeated)
  • L0 DC bus voltage too low
  • L1 DC bus voltage too high
  • P1 High pressure switch opened
  • P3 Compressor drive overcurrent
  • P4 Discharge temperature too high
  • P5 Outdoor coil too hot in cooling
  • P6 Compressor drive (IPM) module protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.10, p.37-38. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.