Navien · Heat pump

FE T3 or T5 probe out of position

Medium severity Navien NAZ

What the control is telling you

The board thinks the coil (T3) or discharge (T5) probe is not on the pipe.

Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)

Likely causes

  • T3 or T5 probe fell off or was moved
  • Damaged sensor
  • Outdoor PCB fault

Test and repair steps

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Look at the T3 coil probe and T5 discharge probe. Make sure each is on its correct pipe and clipped tight.
  3. A probe that has fallen off reads air, not pipe temperature. Put it back in place.
  4. Measure both sensors and compare with the 7.3 R-T Table, p.72.
  5. Probes in place and reading right but code keeps coming: replace the outdoor PCB.

Models that show this code

2 models in Navien NAZ

NAZ17V36NAZ17V60

Other codes on the same units

  • FA Outdoor board memory (EEPROM) fault
  • FB Drive chip memory (EEPROM) fault
  • FC Drive module temperature sensor fault
  • FD Pressure sensor not detected
  • FF High pressure switch reads open all the time
  • HC Lockout: discharge probe off the pipe (FE repeated)
  • HE Repeated condensate-risk faults (F8)
  • IoT LED boot IoT module boot mode

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.7, p.33. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.