Navien · Heat pump
HC Lockout: discharge probe off the pipe (FE repeated)
What the control is telling you
FE happened 3 times within 180 minutes for the T5 discharge probe and the unit has stopped.
Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)
Likely causes
- T5 probe off the discharge line or wrong spot
- Damaged sensor
- Outdoor PCB fault
Test and repair steps
- Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
- Look at the T3 coil probe and T5 discharge probe. Make sure each is on its correct pipe and clipped tight.
- A probe that has fallen off reads air, not pipe temperature. Put it back in place.
- Measure both sensors and compare with the 7.3 R-T Table, p.72.
- Probes in place and reading right but code keeps coming: replace the outdoor PCB.
Models that show this code
2 models in Navien NAZ
Other codes on the same units
- FC Drive module temperature sensor fault
- FD Pressure sensor not detected
- FE T3 or T5 probe out of position
- FF High pressure switch reads open all the time
- HE Repeated condensate-risk faults (F8)
- IoT LED boot IoT module boot mode
- IoT LED pairing IoT module pairing / operation
- IoT Wi-Fi LED color IoT Wi-Fi signal color
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.7, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.