Navien · Heat pump
HE Repeated condensate-risk faults (F8)
What the control is telling you
F8 happened 3 times within 60 minutes. Same checks as F8.
Applies to: NAZ17V36 (24K/36K), NAZ17V60 (48K/60K)
Likely causes
- T4 or T7 sensor out of range
- PCB reading the sensors wrong
Test and repair steps
- Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
- Check T4 and T7 resistance against the 7.3 R-T Table, p.72.
- Compare the CHK readings with a thermometer. Replace the outdoor PCB if they disagree with good sensors.
Models that show this code
2 models in Navien NAZ
Other codes on the same units
- FD Pressure sensor not detected
- FE T3 or T5 probe out of position
- FF High pressure switch reads open all the time
- HC Lockout: discharge probe off the pipe (FE repeated)
- IoT LED boot IoT module boot mode
- IoT LED pairing IoT module pairing / operation
- IoT Wi-Fi LED color IoT Wi-Fi signal color
- LA Compressor speed held back by voltage
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAZ Series Heat Pump Service Manual (V1.00), 4.2.2, p.30. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.