Navien · General

E051 CIP dosing or circulation error

Medium severity WEC

What the control is telling you

Fault during CIP operation. The manual gives two flowcharts under this code.

Applies to: WEC600

Likely causes

  • Low CIP solution in tank
  • Air in CIP line
  • CIP dosing pump or harness faulty
  • Circulation pump or harness faulty
  • TDS sensor or harness faulty

Test and repair steps

  1. Check the remaining amount of CIP solution in the tank.
  2. If air is in the CIP line, reset the error and restart CIP.
  3. If the error occurs again, check whether the CIP dosing pump operates correctly and the CIP solution injection is visibly seen from CI1 and CI2 (or State 52 and 53). If not, replace the CIP dosing pump or its harness.
  4. Check whether the circulation pump runs correctly from CC1 and CC2; some vibration and noise should occur. If not, replace the circulation pump or its harness.
  5. If these are correct, replace the TDS sensor or its harness.

Other codes on the same units

  • E025 Regeneration line #2 blockage error (right)
  • E026 Drain line error (main solenoid path)
  • E027 Drain line error (main solenoid path)
  • E041 TDS sensor error
  • E042 TDS sensor error
  • E060 - E067 Individual sensor errors
  • E070 Install Check Mode drain line error
  • E070 - E084 Install Check Mode errors

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien WEC service manual, p. 63. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.