Navien · Air conditioner
H5 Lockout: low pressure (P2 repeated)
What the control is telling you
P2 happened 5 times within 240 minutes and the unit has stopped.
Applies to: NAA17V36 (24K/36K), NAA17V60 (48K/60K)
Likely causes
- Same as P2: low charge, leak, restriction, airflow, sensor
Test and repair steps
- Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
- Check the pressure sensor plug and wiring.
- Check airflow over the evaporating coil (filter, blower, dirty coil).
- Put gauges on, run the unit and compare the gauge reading with parameter 16 on the CHK display.
- Gauge and display far apart replace the pressure sensor.
- Both agree and are outside the limit system problem. Look for a leak, low charge, restriction or poor vacuum.
- Both agree and are inside the limit replace the outdoor PCB.
Models that show this code
2 models in Navien NAA
Other codes on the same units
- H1 Lockout: outdoor coil too hot (P5 repeated)
- H2 Lockout: high pressure switch (P1 repeated)
- H3 High pressure abnormal (sensor over 3.6 MPa) - heating mode
- H4 Lockout: drive module overheating (P8 repeated)
- H6 Lockout: high discharge temperature (P4 repeated)
- H7 Lockout: low discharge superheat (PC repeated)
- H8 Lockout: T3 probe off the pipe (FE repeated)
- L0 DC bus voltage too low
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAA Series Air Conditioner Service Manual, 3.2.10, p.30-31. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.