Navien · Air conditioner
H3 High pressure abnormal (sensor over 3.6 MPa) - heating mode
What the control is telling you
The manual lists PD/H3 as high pressure protection in heating mode: the pressure sensor read over 3.6 MPa. It is grouped with PD in section 3.2.10. This is an A/C-only model, so if you see it, treat it like PD.
Applies to: Navien NAA17V36 / NAA17V60 R-454B outdoor units
Likely causes
- Pressure sensor wiring loose
- Poor heat transfer at the coil
- Overcharge or restriction
- Pressure sensor shorted or open
- Bad PCB
Test and repair steps
- Power off and wait at least 5 minutes before touching the inverter board.
- Check the pressure sensor plug is tight.
- Put gauges on and compare real pressure with parameter 16 on the display board.
- Gauge and display differ a lot = replace the pressure sensor.
- Both match and out of range = system problem: check for blockage, leak or wrong charge. Check subcooling in Charge mode and superheat against the table.
- Both match and inside range = replace the PCB.
Models that show this code
2 models in Navien NAA
Other codes on the same units
- F9 Line voltage too low or too high
- H0 Communication fault between chips on the outdoor PCB
- H1 Lockout: outdoor coil too hot (P5 repeated)
- H2 Lockout: high pressure switch (P1 repeated)
- H4 Lockout: drive module overheating (P8 repeated)
- H5 Lockout: low pressure (P2 repeated)
- H6 Lockout: high discharge temperature (P4 repeated)
- H7 Lockout: low discharge superheat (PC repeated)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAA Series Air Conditioner Service Manual V1.00 (March 2026), 3.2.10 P2, H5, PD, H3 p.30-31. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.