Navien · Air conditioner
H4 Lockout: drive module overheating (P8 repeated)
What the control is telling you
P8 happened 3 times within 120 minutes and the unit has stopped.
Applies to: NAA17V36 (24K/36K), NAA17V60 (48K/60K)
Likely causes
- Same as P8
Test and repair steps
- Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
- Make sure the refrigerant cooling cover over the drive module is screwed down tight.
- Remove the cover and check the white thermal paste. Re-apply it if uneven.
- Run the unit and watch. Still tripping: replace the outdoor PCB.
Models that show this code
2 models in Navien NAA
Other codes on the same units
- H0 Communication fault between chips on the outdoor PCB
- H1 Lockout: outdoor coil too hot (P5 repeated)
- H2 Lockout: high pressure switch (P1 repeated)
- H3 High pressure abnormal (sensor over 3.6 MPa) - heating mode
- H5 Lockout: low pressure (P2 repeated)
- H6 Lockout: high discharge temperature (P4 repeated)
- H7 Lockout: low discharge superheat (PC repeated)
- H8 Lockout: T3 probe off the pipe (FE repeated)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAA Series Air Conditioner Service Manual, 3.2.15, p.39. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.