Navien · Air conditioner

H8 Lockout: T3 probe off the pipe (FE repeated)

High severity Navien NAA

What the control is telling you

FE happened 3 times within 120 minutes for the T3 coil probe and the unit has stopped.

Applies to: NAA17V36 (24K/36K), NAA17V60 (48K/60K)

Likely causes

  • T3 probe off the pipe or wrong spot
  • Damaged sensor
  • Outdoor PCB fault

Test and repair steps

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Look at the T3 coil probe and T5 discharge probe. Make sure each is on its correct pipe and clipped tight.
  3. A probe that has fallen off reads air, not pipe temperature. Put it back in place.
  4. Measure both sensors and compare with the 6.3 R-T Table, p.61.
  5. Probes in place and reading right but code keeps coming: replace the outdoor PCB.

Models that show this code

2 models in Navien NAA

NAA17V36NAA17V60

Other codes on the same units

  • H4 Lockout: drive module overheating (P8 repeated)
  • H5 Lockout: low pressure (P2 repeated)
  • H6 Lockout: high discharge temperature (P4 repeated)
  • H7 Lockout: low discharge superheat (PC repeated)
  • L0 DC bus voltage too low
  • L1 DC bus voltage too high
  • P1 High pressure switch opened
  • P2 Low pressure protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAA Series Air Conditioner Service Manual, 3.2.7, p.26. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.