Navien · Air conditioner

L0 DC bus voltage too low

High severity Navien NAA

What the control is telling you

The inverter DC bus voltage on the outdoor board is out of range.

Applies to: NAA17V36 (24K/36K), NAA17V60 (48K/60K)

Likely causes

  • Supply voltage problem
  • Outdoor PCB fault

Test and repair steps

  1. Measure line voltage at the unit. Fix the supply if it is off.
  2. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  3. Supply is good and the code returns replace the outdoor PCB.

Models that show this code

2 models in Navien NAA

NAA17V36NAA17V60

Other codes on the same units

  • H5 Lockout: low pressure (P2 repeated)
  • H6 Lockout: high discharge temperature (P4 repeated)
  • H7 Lockout: low discharge superheat (PC repeated)
  • H8 Lockout: T3 probe off the pipe (FE repeated)
  • L1 DC bus voltage too high
  • P1 High pressure switch opened
  • P2 Low pressure protection
  • P3 Compressor drive overcurrent

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAA Series Air Conditioner Service Manual, 3.2.19, p.44. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.