E808 Inverter trip: Overcurrent at compressor current limit

High severity Navien NAE

What the control is telling you

Inverter trip error shown after alarm 858 occurred four times. Manual reset needed (display shows 808).

Applies to: NAE28V3622A1, NAE28V6022A1

Test and repair steps

  1. Turn off power at the disconnect before opening the unit.
  2. Check the outdoor coil for clogging and clean it. Make sure the outdoor fan motor works.
  3. Check the suction pressure transducer and suction temperature sensor.
  4. The inverter drops to a lower speed stage on its own.
  5. Check voltage against the rating plate.
  6. Check incoming power leads and the leads to the compressor plug.
  7. Check refrigerant amount.
  8. Replace the inverter, then the compressor if needed.

Models that show this code

2 models in Navien NAE

NAE28V3622A1NAE28V6022A1

Other codes on the same units

  • E804 Inverter trip: PFCM current A error
  • E805 Inverter trip: PFCM current B error
  • E806 Inverter trip: Input voltage sensor error
  • E807 Inverter trip: Software compressor overcurrent
  • E809 Inverter trip: Overcurrent at ID current limit
  • E810 Inverter trip: Hardware compressor overcurrent
  • E811 Inverter trip: PFC overcurrent
  • E812 Inverter trip: Estimator fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAE I&O manual (07/2026), 7.1 Error table and 7.2.25, p.59. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.