E806 Inverter trip: Input voltage sensor error

High severity Navien NAE

What the control is telling you

Inverter trip error shown after alarm 856 occurred four times. Manual reset needed (display shows 806).

Applies to: NAE28V3622A1, NAE28V6022A1

Likely causes

  • Voltage imbalance or sudden swings
  • PFCM current sensor or connector failure
  • Inverter damage
  • Poor sensor or connector contact
  • Momentary voltage rise or noise
  • Leakage current from poor grounding

Test and repair steps

  1. Turn off power at the disconnect before opening the unit.
  2. Check the sensors and connectors.
  3. Measure input voltage and compare with the rated range.
  4. Check the EMI filter.
  5. Measure ground resistance and re-ground if needed.
  6. Replace the inverter if needed.
  7. It may be temporary electrical noise, so recheck after a reboot.

Models that show this code

2 models in Navien NAE

NAE28V3622A1NAE28V6022A1

Other codes on the same units

  • E802 Inverter trip: Compressor current sensor error
  • E803 Inverter trip: DC link sensor error
  • E804 Inverter trip: PFCM current A error
  • E805 Inverter trip: PFCM current B error
  • E807 Inverter trip: Software compressor overcurrent
  • E808 Inverter trip: Overcurrent at compressor current limit
  • E809 Inverter trip: Overcurrent at ID current limit
  • E810 Inverter trip: Hardware compressor overcurrent

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAE I&O manual (07/2026), 7.1 Error table and 7.2.23, p.58. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.