Kinghome · Heat pump
H4 Overload protection (high condensing pressure)
What the control is telling you
Condensing pressure exceeded its protection value on Ultranixx units.
Applies to: Kinghome Ultranixx Eco KD24UHO to KD60UHO outdoor units with KD..UHI air handlers; Kinghome Ultranixx cold-climate KU36UHO and KU60UHO outdoor units with KU..UH2I and KD..UHI air handlers
Likely causes
- Blocked outdoor or indoor coil
- Ambient above operating range
- Overcharge
Test and repair steps
- Clean the coils.
- Check ambient limits.
- Release a proper amount of refrigerant if overcharged.
- Replace the drive board then compressor if the code persists.
Models that show this code
18 models in Kinghome Ultranixx Eco, Kinghome Ultranixx
Other codes on the same units
- F2 Sensor fault (indoor coil or outdoor condenser)
- F3 Outdoor ambient temperature sensor fault
- F6 Frequency limit for overload / ODU tube sensor fault
- H3 Compressor overload protection
- H5 IPM module protection
- H6 Fan motor feedback fault (indoor or outdoor)
- H7 Compressor out-of-step
- P0 Compressor minimum-frequency test / driver reset
Sequence of operation
What the unit does around this code, step by step.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Kinghome Ultranixx Eco KD24-60UHO service manual, sec. 3.3-3.4; Kinghome Ultranixx cold-climate KU36/60UHO service manual GC202306, sec. 3.3-3.4. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.