Kinghome · Heat pump

H6 Fan motor feedback fault (indoor or outdoor)

High severity Kinghome KM HEDIKinghome KM HT1DIKinghome KM HF1DIKinghome Ultranixx EcoKinghome Ultranixx

What the control is telling you

On the wall units H6 means the indoor DC fan motor gives no speed feedback. On Ultranixx units H6 is the outdoor DC fan: no feedback within 30 s of start.

Applies to: Kinghome KM09HEDI, KM12HEDI, KM18HEDI wall mini-splits; Kinghome KM09HT1DI, KM12HT1DI, KM18HT1DI, KM24HT1DI wall mini-splits; Kinghome KM09HF1DI to KM24HF1DI wall mini-splits (Gree GFH..DA/DB); Kinghome Ultranixx Eco KD24UHO to KD60UHO outdoor units with KD..UHI air handlers; Kinghome Ultranixx cold-climate KU36UHO and KU60UHO outdoor units with KU..UH2I and KD..UHI air handlers

Likely causes

  • Motor feedback or control plug loose
  • Motor stalled or failed
  • Fault in the board's speed detection
  • Program/board mismatch on a new motor (Ultranixx)

Test and repair steps

  1. Check the motor plugs.
  2. Spin the blade by hand.
  3. Measure motor supply and feedback voltages (wall units).
  4. Replace the motor, then the board.

Models that show this code

30 models in Kinghome KM HEDI, Kinghome KM HT1DI, Kinghome KM HF1DI, Kinghome Ultranixx Eco, Kinghome Ultranixx

KD24UHIKD24UHOKD30UHIKD30UHOKD36UHIKD36UHOKD42UHIKD42UHOKD48UHIKD48UHOKD60UHIKD60UHOKM09HEDIKM09HF1DIKM09HT1DIKM12HEDIKM12HF1DIKM12HT1DIKM18HEDIKM18HF1DIKM18HT1DIKM21HF1DIKM24HF1DIKM24HT1DIKU24UH2IKU36UH2IKU36UHOKU48UH2IKU60UH2IKU60UHO

Other codes on the same units

  • H2 Defrosting mode 2 selected (remote display)
  • H3 Compressor overload protection
  • H4 Overload protection (high condensing pressure)
  • H5 IPM module protection
  • H7 Compressor out-of-step
  • L3 Outdoor DC fan motor fault
  • L9 Power limit protection
  • P0 Compressor minimum-frequency test / driver reset

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Kinghome KM09-12-18HEDI service manual, sec. 9.3 status table and 9.4 troubleshooting; Kinghome KM09-12-18-24HT1DI service manual, sec. 9.1 error code list; Kinghome KM09-24HF1DI service manual, sec. 11.1 error code list; Kinghome Ultranixx Eco KD24-60UHO service manual, sec. 3.3-3.4; Kinghome Ultranixx cold-climate KU36/60UHO service manual GC202306, sec. 3.3-3.4. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.