E3 Low pressure protection / low-pressure sensor fault
What the control is telling you
The system tripped on low refrigerant-side pressure, usually from a blocked system or lost charge. On Ultranixx outdoor units E3 is the low-pressure trip and lower-case e3 means the low-pressure sensor signal is out of range for 30 s.
Applies to: Kinghome KM09HT1DI, KM12HT1DI, KM18HT1DI, KM24HT1DI wall mini-splits; Kinghome KM09HF1DI to KM24HF1DI wall mini-splits (Gree GFH..DA/DB); Kinghome Ultranixx Eco KD24UHO to KD60UHO outdoor units with KD..UHI air handlers; Kinghome Ultranixx cold-climate KU36UHO and KU60UHO outdoor units with KU..UH2I and KD..UHI air handlers
Likely causes
- Low charge or refrigerant leak
- Closed service valve or blocked line
- Blocked indoor filter or duct in cooling, outdoor ambient too low
- Fan not working properly
- Faulty low-pressure switch/sensor or poor plug contact (e3)
Test and repair steps
- Check for a leak and verify the charge.
- Open the service valves fully and check for line restrictions.
- Clean the filter and confirm both fans run normally.
- Test the low-pressure switch or sensor and its connector; replace if faulty.
- Replace the control board only if the sensor and wiring are good.
Models that show this code
27 models in Kinghome KM HT1DI, Kinghome KM HF1DI, Kinghome Ultranixx Eco, Kinghome Ultranixx
Other codes on the same units
Sequence of operation
What the unit does around this code, step by step.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Kinghome KM09-12-18-24HT1DI service manual, sec. 9.1 error code list; Kinghome KM09-24HF1DI service manual, sec. 11.1 error code list; Kinghome Ultranixx Eco KD24-60UHO service manual, sec. 3.3-3.4; Kinghome Ultranixx cold-climate KU36/60UHO service manual GC202306, sec. 3.3-3.4. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.