Kinghome · Heat pump

08 Debug menu item 08: refrigerant recovery

Menu / mode display Kinghome Ultranixx

What the display is showing

Menu item 08 on the KU outdoor board display switches the refrigerant recovery (pump-down) function on or off. ON starts it and OF cancels it. It is saved with SW1.

Applies to: Kinghome Ultranixx cold-climate KU36UHO and KU60UHO outdoor units with KU..UH2I and KD..UHI air handlers

What to do

  1. Hold SW1 about 5 s, short-press SW1 until 08 shows.
  2. SW2 or SW3 chooses ON or OF.
  3. Short-press SW1 to save.

Models that show this code

6 models in Kinghome Ultranixx

KU24UH2IKU36UH2IKU36UHOKU48UH2IKU60UH2IKU60UHO

Other codes on the same units

  • 01 Forced operation value: cooling
  • 02 Forced operation value: heating
  • 06 Debug menu item 06: forced defrost
  • 09 Debug menu item 09: forced operation
  • C4 ODU jumper cap error
  • E1 High pressure protection / high-pressure sensor fault
  • E3 Low pressure protection / low-pressure sensor fault
  • F2 Sensor fault (indoor coil or outdoor condenser)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Kinghome Ultranixx cold-climate KU36/60UHO service manual GC202306, sec. 2.3.6 refrigerant recovery control. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.