Gree · Heat pump

E6 Indoor/outdoor communication fault

High severity Gree SapphireGree Livo GEN4Gree Vireo GEN3Gree Multi21+

What the control is telling you

The indoor and outdoor boards cannot talk to each other. In cooling the compressor stops; in heating the whole unit stops. On the Multi21+ it can show on only some heads.

Applies to: Gree Sapphire 9-24k (SAP..HP230V1A), Livo GEN4 30-36k (4LIV..HP230V1A), Vireo GEN3 9-24k (3VIR..HP115/230V1A), Multi21+ 18-24k multi-zone (MULTI..HP230V1CO)

Likely causes

  • Interconnect wiring wrong, loose or damaged
  • Wires in the electrical box loose
  • Mismatched indoor/outdoor boards or display board
  • Indoor board communication circuit failed
  • Outdoor board (AP1) communication circuit failed

Test and repair steps

  1. Warning: Kill power before working on terminals.
  2. Check the interconnect wiring terminal by terminal against the wiring diagram and tighten every screw.
  3. Inspect the cable for damage and replace it if needed.
  4. Confirm the indoor and outdoor units (and display board) are a matching combination.
  5. Use a communication checker if available to find which side has failed.
  6. Replace the indoor board or outdoor board (AP1) on the side that fails.

Models that show this code

14 models in Gree Sapphire, Gree Livo GEN4, Gree Vireo GEN3, Gree Multi21+

3VIR09HP115V1A3VIR09HP230V1A3VIR12HP115V1A3VIR12HP230V1A3VIR18HP230V1A3VIR24HP230V1A4LIV30HP230V1AH4LIV36HP230V1AHMULTI18HP230V1COMULTI24HP230V1COSAP09HP230V1AHSAP12HP230V1AHSAP18HP230V1AHSAP24HP230V1AH

Other codes on the same units

  • E2 Indoor coil freeze protection (status)
  • E3 Low pressure protection
  • E4 Compressor discharge temperature too high
  • E5 Overcurrent protection (whole unit)
  • E7 Mode conflict between indoor units (status)
  • E8 High temperature / overload protection
  • E9 Cold air prevention (status)
  • F0 Low refrigerant / refrigerant blocked protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree Sapphire 9-12k (SAP09-12HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Sapphire 18-24k (SAP18-24HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Livo GEN4 30-36k (4LIV30-36HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Vireo GEN3 9-24k (3VIR..HP115-230V1A) service GREE_VIREOGEN3_SERVICE_090921.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Multi21+ multi-zone 18-24k (MULTI18-24HP230V1CO) service.pdf - section 9.1 Malfunction status sheet / 9.2 Malfunction Checking and Elimination. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.