Gree · Heat pump

E8 High temperature / overload protection

Medium severity Gree SapphireGree Livo GEN4Gree Vireo GEN3Gree Multi21+

What the control is telling you

The coil temperature (outdoor coil in cooling, indoor coil in heating) got too high, so the compressor stops.

Applies to: Gree Sapphire 9-24k (SAP..HP230V1A), Livo GEN4 30-36k (4LIV..HP230V1A), Vireo GEN3 9-24k (3VIR..HP115/230V1A), Multi21+ 18-24k multi-zone (MULTI..HP230V1CO)

Likely causes

  • Outdoor temperature above the operating range (above 53°C/127°F)
  • Poor heat rejection: dirty coil or blocked airflow
  • Indoor or outdoor fan not running properly
  • Fan capacitor or fan motor failed
  • Board fault

Test and repair steps

  1. Check the outdoor ambient; above 53°C the trip is normal protection.
  2. Clean the coils and clear the space around the units.
  3. Check that both fans run; check fan wiring connections.
  4. Test the fan capacitor and motor (where used) and replace as needed.
  5. If all of the above check good, replace the board.

Models that show this code

14 models in Gree Sapphire, Gree Livo GEN4, Gree Vireo GEN3, Gree Multi21+

3VIR09HP115V1A3VIR09HP230V1A3VIR12HP115V1A3VIR12HP230V1A3VIR18HP230V1A3VIR24HP230V1A4LIV30HP230V1AH4LIV36HP230V1AHMULTI18HP230V1COMULTI24HP230V1COSAP09HP230V1AHSAP12HP230V1AHSAP18HP230V1AHSAP24HP230V1AH

Other codes on the same units

  • E4 Compressor discharge temperature too high
  • E5 Overcurrent protection (whole unit)
  • E6 Indoor/outdoor communication fault
  • E7 Mode conflict between indoor units (status)
  • E9 Cold air prevention (status)
  • F0 Low refrigerant / refrigerant blocked protection
  • F1 Indoor room air sensor open or shorted
  • F2 Indoor coil sensor open or shorted

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Gree Sapphire 9-12k (SAP09-12HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Sapphire 18-24k (SAP18-24HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Livo GEN4 30-36k (4LIV30-36HP230V1A) service.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Vireo GEN3 9-24k (3VIR..HP115-230V1A) service GREE_VIREOGEN3_SERVICE_090921.pdf - section 9.1 Error Code List / 9.2 Procedure of Troubleshooting; Gree Multi21+ multi-zone 18-24k (MULTI18-24HP230V1CO) service.pdf - section 9.1 Malfunction status sheet / 9.2 Malfunction Checking and Elimination. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.