FlowMax combi boiler error codes

24 codes (13 faults, 11 normal display and menu codes), plus 2 settings tables.

CodeMeaningSeverity / type
07Flue test (chimney sweeper) function activeMenu / mode display
08Frost protection activeNormal status
22Fan frequency readout (parameter 22)Menu / mode display
28Legionella prevention cycle activeNormal status
31Incompatible remote controlLow
E01Ignition / ionization lockout (no flame)High
E02Safety (overheat) thermostat or air pressure switch trippedHigh
E03Flue gas thermostat / exhaust thermofuse trippedHigh
E05Heating (supply) sensor faultMedium
E06Domestic hot water (DHW) sensor faultMedium
E12DHW storage tank (cylinder) sensor faultMedium
E14Air pressure switch trippedHigh
E16Fan (blower) faultHigh
E22Parameter programming requestMedium
E35Flame detection fault (false flame)High
E42Fan speed control board faultHigh
H2OLow water pressure in heating circuitMedium
Curve numberCompensation curve number displayMenu / mode display
OFFSwitched off, frost protection still activeNormal status
Outdoor tempOutdoor temperature readoutMenu / mode display
PL 0Parameter menu enteredMenu / mode display
Summer mode symbolSummer mode selected (hot water only)Normal status
Summer/Winter mode symbolsSummer and winter mode selected (heating and hot water)Normal status
Winter mode symbolWinter mode selected (heating only)Normal status

Settings and specs

Installation clearances

Clearances · FlowMax condensing combi (FLOWMAX-90/120)

LocationService clearance (in)To combustibles
X (side)00 in
Y (side)00 in
L16-
H24-
A (above)120 in from jacket top
B (below)12-
Front-0 in
Rear-0 in
  • Wall-mount on a flat, solid vertical wall that can carry the weight.
  • Letters follow fig. 1 of the manual; L and H are the clearance zone in front/around the unit as drawn.
  • Closet installation: 0 in front; alcove allowed.

Source: FlowMax FLOWMAX-120 Instruction Manual (ManualsLib 769807), 3.3 Installing the water heater fig. 1 and item d, p.25; Warning label p.15

Hot water scald risk by temperature

Specifications · FlowMax condensing combi (FLOWMAX-90/120)

Temperature settingTime to 2nd/3rd degree burn (adult skin)
Over 170°FNearly instantaneous
160°FAbout 1/2 second
150°FAbout 1-1/2 seconds
140°FLess than 5 seconds
130°FAbout 30 seconds
120°F or lessMore than 5 minutes
  • 120°F lowers scald risk; children, elderly and disabled people burn faster.
  • Fit a tempering (mixing) valve if water is stored or set hotter, e.g. with parameter 1 = 03 (up to 160°F).

Source: FlowMax FLOWMAX-90 User Manual (ManualsLib 763385), Danger - Table Risk of Scalds (image), p.7; FlowMax FLOWMAX-120 Instruction Manual (ManualsLib 769807), same table (image), p.14

Models covered

FLOWMAX-120FLOWMAX-90

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.