FlowMax · Combi boiler
E05 Heating (supply) sensor fault
What the control is telling you
The heating NTC sensor reads out of range. Sensor is 10 kOhm at 25°C (77°F). Note: the 120 troubleshooting table text is misaligned in this area; meaning is taken from the diagnostics list and user manual.
Applies to: FLOWMAX-90, FLOWMAX-120
Likely causes
- Sensor faulty or out of calibration
- Sensor wire disconnected or wet
Test and repair steps
- Turn off power before working on sensor wiring.
- Check the sensor connector and wiring for looseness, damage or moisture.
- Unplug the sensor and measure resistance about 10 kOhm at 25°C (77°F).
- Replace the sensor if the reading is open, shorted or far off.
- Restart and confirm the code clears.
Settings for these units
- Installation clearances · FlowMax condensing combi (FLOWMAX-90/120)
- Hot water scald risk by temperature · FlowMax condensing combi (FLOWMAX-90/120)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: FlowMax FLOWMAX-120 Instruction Manual, 6.10 Troubleshooting table, p.66; FlowMax FLOWMAX-120 Instruction Manual, 6.11 Diagnostics error code list, p.67; FlowMax FLOWMAX-90 User Manual, Diagnostics - Error codes, p.8-9. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.